Public Article
-
verified
Geological investigation of the Upper Part of Memouniat FormatioThe Optimum location of Gas Turbine to Improve the Vol...
ISSN: 2789 - 2239Publisher: author   
Geological investigation of the Upper Part of Memouniat FormatioThe Optimum location of Gas Turbine to Improve the Vol...
Indexed in
Technology and Engineering
ARTICLE-FACTOR
1.3
Article Basics Score: 2
Article Transparency Score: 3
Article Operation Score: 2
Article Articles Score: 2
Article Accessibility Score: 3
SUBMIT PAPER ASK QUESTION
International Category Code (ICC):
ICC-1802
Publisher: Bright Star University, Libya.
International Journal Address (IAA):
IAA.ZONE/2789404962239
eISSN
:
2789 - 2239
VALID
ISSN Validator
Abstract
The voltage stability is very important term in power system stability. This work, study the impact of the connection point of generator to the electrical network on voltage stability. The case study used in this work is the Libyan eastern network that suffer from load shedding due to voltage instability. Even though the new generation unit connected at Tobruk power station, the northeastern region still suffer from the voltage instability. Due to the cold weather during the winter season, the load demand increase which leads to voltage collapse. The NEPLAN software is used to model and analysis the network, switchgears, transformers, 220 KV stations and lines had modeled to do the power flow analysis. The impact of this gas-generation unit connection point on the voltage at four different 220 KV buses in the network was tested. Moreover, the study found the best bus that the unit to be connected is at Al-Bayda bus bar. In addition, t...